BAUMER Level Switch LFFS
-
Sensor - Radiated signal:100...180 MHZ
-
Sensor - Process connection:Hygienic: G1/2, 3-A/DN38 or sliding connection
-
Sensor - Insulating material:PEEK Natura
-
Housing:Stainless Steel, W1.4301/AISI 304
-
Process connection:Stainless Steel, W1.4404/AISI 316 L
-
Amb. temperature:-40...85 °C
-
Process temperature - Std. & 3-A/DN38:-40...115 °C
-
Process temperature - Sliding connection:-40...200 °C
-
Process temperature - < 1 hour, Tamb < 60 °C:-40...140 °C
-
Media pressure - Standard G½ hygienic:< 100 bar
-
Media pressure - 3-A DN38:< 40 bar
-
Media pressure - Sliding connection:< 16 bar
-
Vibrations:IEC 60068-2-6, GL test2
-
Power supply:12,5...36 VDC, 35 mA max.
-
Damping:0...10 sec.
-
Power-up time:<2 sec.
-
Reaction time:0.1 sec. (100 mS)
Description
BAUMER Level Switch LFFS
Special Features
- Wetted parts in acid-proof, stainless steel and PEEK
- Compact, food compatible, hygienic design
- Hygienic connections conform to 3-A standards, FDA demands and EHEDG guidelines
- Precise switching point without calibration
- Process temperature -40...200 °C
- Measures media with DK-values >1.5 (DK = Dielectrical Constant)
- Not influenced by foam
- LED switch indicator
- Maintenance free
- Suitable for media separation measurement
- Configurable by FlexProgrammer 9701
- ATEX approval for gas and dust
- WHG approval (leakage and overfill)
Technical